Natural gas detector JT-ZL2010
- Stock: In Stock
- Model: FIR-JT-ZL2010
- EAN: 5904507904791
- Weight: 196g
- Dimensions: 112mm x 86mm x 33.50mm
Firesco JT-ZL2010 detector is designed to monitor rooms for the presence of natural gas (LNG, methane CH4). It is based on a semiconductor sensor, characterized by high accuracy and durability up to 5 years.
It has been calibrated to trigger an alarm at a concentration of ≤7% LEL ±3% LEL (Lower Explosive Limit). for methane. If a gas leak is detected, an optical and acoustic alarm is activated. The device has a self-diagnostic system that monitors the sensor and internal circuits. In case of incorrect operation, a yellow LED lights up to indicate that a fault has been detected.
It is powered by 220-240V AC 50/60Hz via a 150 cm long cable terminated with a European type C plug. The device is manufactured in accordance with Polish standard PN-EN50194-1:2009. It has a certificate confirming that it meets the above requirements. standards issued by an independent European research unit.
JT-ZL2010 detector is intended for installation on the internal walls of the building, in rooms where the temperature does not drop below 0°C and rises above +55°C and humidity does not exceed 95% RH.
APPLICATION
Kitchen rooms equipped with a gas stove, boiler rooms with natural gas stoves, rooms where there are gas devices such as: valves, gas meters, gas pipes, school chemical and physics laboratories.
ADVANTAGES
- Semiconductor sensor with high accuracy and durability up to 5 years
- Optical-acoustic signaling at a concentration of 7% LEL
- System for monitoring the efficiency of the device
- Test button to control and operate the device
- Simple installation and operation
- Signalization of incorrect operation and end of service life
- Aesthetic and durable housing
- Compliance with the EN50194-1:2009 standard confirmed by an independent European research unit
- 2-year warranty
Product information | |
Sensor | Semiconductor |
Gases detected | Natural gas (methane CH4) |
Alarm threshold | ≤ 7% LEL ±3% LEL |
Power signaling | The green LED is lit |
Alarm signaling | Optical – red LED is flashing Acoustic – siren with an intensity of 85 dB at a distance of 1 m |
Signaling the end of the service life | Sound and light |
Signaling of incorrect operation | The yellow LED is lit |
Test / Hush Button | To control and operate the device |
Sensor durability | Up to 5 years |
Housing | White color |
Additionally included | Mounting pins Mounting bracket User manual in Polish |
Power | |
Power source | Mains power supply, 220-240V AC 50/60Hz, 1.5 m cable, european type C plug |
Power consumption | 0.5W / 4W |
Working and storage conditions | |
Working conditions | Temperature: 0°C ~ 55°C Humidity: < 95% RH, non-condensing |
Storage conditions | Temperature: -25°C ~ 55°C Humidity: < 95% RH, non-condensing |
Quality and safety | |
Certificates and approvals | PN-EN50194-1:2009, confirmed by an independent, notified testing unit CE mark |
Warranty | 2 years |